Certified Fire Dampers
Product description
According to the newest revisions of SOLAS and IMO regulations we have developed and certified a new generation of fire-dampers. Almost every fire-damper in use today is only classified as a normal shut-off-damper, which are no longer allowed to be used for this application. Below you find the description of our standard-program for certified fire dampers. A very flexible production allows special requirements to be met as well.
IGW-Firedamper, deck type
1 bladed, round Ø1400 mm
Insulation Class A-60
After fire test acc. SOLAS 1974 and IMO Res. A 754 (18)
Tested: TÜV Nord, Bramdhaus Hamburg
Certified: Lloyd's Register of Shipping MED
According to: SOLAS 1974 and IMO Res. A 754 (18)
Main characteristics
Decktype 1-bladed round Ø 315 – 1800 mm
Insulationclass A-0 – A-60
Casingthickness 3 - 12 mm
Materials S235JRG, 1.4301, 1.4571
Drivetypes manual, electric, pneumatic, hydraulic, linear or rotary drives
Triggering without/with temp.release 70°C
Insulation certified mineralwool acc. to fire-protection-rules SOLAS/MED/IMO
Surfacetreatment Primer, Finish hot dip galvanised
Übersicht der Temperaturanforderungen der Brandschutzklassen
Type | Insulation Cl. | Temperature/Period Fire Side | Temperature/Period Non Fire Side |
---|---|---|---|
Deck / Deck | A-0 | 950°C – 1h | n.a. |
Deck / Deck | A-15 | 740°C – 15 min. | +140°C – 15 min. |
Deck / Deck | A-30 | 840°C – 30 min. | +140°C – 30 min. |
Deck / Deck | A-60 | 950°C – 1h | +140°C – 1h |